Die genannten Informationen entbinden den Kunden nicht von selbständigen Applikationsprüfungen.
Suitability of this product for its intended use and any associated risks must be determined by the end customer/buyer in its final application.
35 35 TIGER ELECTRONICS THERMAL MANAGEMENT TIGER ELECTRONICS FANS + ACCESSORIES Die genannten Informationen entbinden den Kunden nicht von selbständigen Applikationsprüfungen.
Suitability of this product for its intended use and any associated risks must be determined by the end customer/buyer in its final application.
• Filter changeable from outside • Safe, lockable • Impact resistant • Weather proof The outdoor filter fan can be used in outdoor enclosures where warm air has to be dissipated on account of increased thermic development.
To clean and exchange the filter mat, it is only necessary to open the lockable door of the outdoor hood.
A protection type of IP55 is achieved due to the special design of the hood and the use of fine filter mats.
The plastic casing is impact resistant, highly weather proof and resistant to UV light.
• Filterwechsel von außen • Sicher, abschließbar • Schlagfest • Befestigung von unzugänglicher Schrankinnenseite • Witterungsbeständig Der Outdoor-Filterlüfter wird in Schränken und Gehäusen im Außenbereich eingesetzt, aus denen warme Luft aufgrund erhöhter Wärmeentwicklung (Sonneneinstrahlung, Verlustwärme von Einbauten) abgeführt werden muss.
Das Gehäusematerial besteht aus schlagzähem Kunststoff und weist eine hohe Witterungs- und UV-Beständigkeit auf.
Bei Verwendung von Feinfiltermatten sowie durch die Konstruktion der Haube wird eine hohe Schutzart von IP55 erreicht.
Zur Reinigung oder zum Wechsel der Filtermatte muss lediglich die verschließ- bare Klappe der Outdoor-Haube geöffnet werden, das Öffnen des Schranks (Sicherheitsrisiko) erübrigt sich.
Axial fan, ball bearing service life min.
50,000h at 25°C/77°F (65% RH) fan body aluminium, rotor plastic Connection 2 wires with pressure clamps 2.5mm², length 100mm Filter fan and exit filter casing casing material high impact plastic ASA, light grey burning behaviour according to UL94 H-B high resistance to weather and UV Mounting frame with double industrial adhesive band for fixing to the outside of enclosure certain operating circumstances can make the additional use of screws necessary (see drilling template) included in the delivery of the filter fans is a template for the enclosure cut-out.
Filter mat (media) F5 acc.
to DIN EN 779, filtering degree 98% Filter material synthetic fibre with progressive construction, temperature resistant to 100°C, self-extinguishing class F1 moisture resistant to 100% RH Operating/ Storage temperature -45 to +70°C (-49 to +158°F) Protection type IP55 Protection class I (earthed) Approvals UL The hood is fixed permanently to the enclosure from the inside using screws.
Filter mats can be easily changed from outside the enclosure through the lockable door in the hood.
Outdoor Filter Fan - Outdoor Filterlüfter FF 018 Series Art.
No.
Operating Air volume, Current Power Average Depth in Enclosure Weight Approvals voltage free flow noise level enclosure cut-out (approx.) Art.
Nr.
Betriebsspannung Kühlluft- Betriebs- Leistungs- Schalldruck Einbautiefe Montage Gewicht Approbationen fördermenge strom aufnahme ausschnitt (ca.) 01821.0-00 230VAC, 50Hz 20m³/h 100 mA 15W 40dB (A) 62mm 125x125mm+0.4 1,20kg UL 01821.0-02 120VAC, 50Hz 23m³/h 180 mA 15W 40dB (A) 62mm 125x125mm+0.4 1,20kg UL Exit Filter - Austrittsfilter EF 118 Series Art.
No.
Depth in enclosure Enclosure cut-out Weight (approx.) Filter mat Protection type Art.
Nr.
Einbautiefe Montageauschnitt Gewicht (ca.) Filtermatte Schutzart 11821.0-00 16mm 125x125mm+0.4 0,60kg F5 acc.
to DIN EN 779, filtering degree 98% IP55 Filter Mats - Filtermatten FFM 086 / FFM 086 Filter mat - Filtermatte 247 x 247mm F5 (1 packing unit = 3 pcs.) Art.
No.
08607.0-00 Axiallüfter, Kugellager Lebensdauer min.
50.000 h bei 25 °C/ 77 °F (rF 65 %) Lüfterrahmen Aluminium, Rotor Kunststoff Anschluss 2 Litzen, 100 mm lang, mit schraubenlosen Druckklemmen 2,5 mm² Filterlüftergehäuse und Austrittsfilter Gehäusematerial schlagzäher Kunststoff ASA nach UL94 H-B, lichtgrau.
Hohe Witterungs- und UV-Beständigkeit.
Einbaurahmen Mit doppelseitigem Industrieklebeband zur Befestigung an der Schrank außenwand.
Bestimmte Einsatz bedingungen können eine zusätzliche Schraubbefestigung erforderlich machen (siehe Bohrbild).
Filtermatte F5 nach DIN EN 779, mittlerer Abscheidegrad 98 % Filtermaterial Kunststofffaser mit progressivem Aufbau, temperaturbeständig bis 100 °C, selbstverlöschend Klasse F1.
Feuchtigkeitsbeständig bis 100 % rF.
Einsatz-/ Lagertemperatur -45 bis +70 °C (-49 bis +158 °F) Schutzart IP55 Schutzklasse I (Schutzleiter) Approbationen UL Die Haube wird von innen montiert und mit Schrauben dauerhaft am Schaltschrank befestigt.
Die Filtermatten können, durch die abschließbare Haubenklappe, einfach von außen ausgewechselt werden.
Outdoor Filter Fan Outdoor-Filterlüfter Drilling template for mounting frame Bohrbild für Einbaurahmen View from rear Ansicht Rückseite Outdoor Exit filter Outdoor-Austrittsfilter Outdoor Filter Fan • Outdoor Filterlüfter FF 018 TIGER electronics