36 36 TIGER ELECTRONICS THERMAL MANAGEMENT TIGER ELECTRONICS FANS + ACCESSORIES Technische Änderungen vorbehalten.
Alle Angaben ohne Gewähr.
Specifications are subject to change without notice.
Errors and omissions excepted.
1 m³/min = 35.3 CFM 1 Pa = 0.10197 mmH2O = 0.00401 inH2O Technische Änderungen vorbehalten.
Alle Angaben ohne Gewähr.
Specifications are subject to change without notice.
Errors and omissions excepted.
• Very low noise • Minimal depth in enclosure • High through-flow air volume • Uniform air circulation • High reliability • Time-saving installation Roof filter fans and roof exit filters find use in enclosures, from which warm air has to be diverted due to increased heat development.
The ready-to-connect and low-noise roof filter fan, which houses four axial fans, is used to expel warm air from within the enclosure which has been generated by the stray power of the components.
The roof exit filter provides passive ventilation.
• Geräuscharm • Geringe Einbautiefe • Hoher Luftdurchsatz • Hohe Betriebssicherheit • Zeitsparende Montage und • Filtermattentausch Dach-Filterlüfter werden zur Kühlung von Schrän- ken und Gehäusen mit elektrischen/ elektronischen Einbauten eingesetzt.
Durch die Abführung erwärm- ter Innenluft und die Zuführung gefilterter, kühlerer Umgebungsluft wird die Innentemperatur gesenkt.
Der Luftstrom verhindert die Bildung von Wärmene- stern und schützt die Bauteile vor Überhitzung.
Mit dem Einsatz dieser geräuscharmen Dach-Filterlüfter erreicht man eine gleichmäßige Luftumwälzung im Gehäuse und damit eine besonders hohe Betriebssi- cherheit.
Die Haube kann für den Mattentausch ohne Werkzeug geöffnet werden.
Zur passiven Entlüftung ist der DachAustrittsfilter geeignet.
Axial fans, ball bearing service life 50,000h at 25°C/ 77°F (65% RH) fan body aluminium, rotor plastic Connection 3-pole clamp for 2.5mm² Casing plastic acc.
to UL94 V-0/ lacquered steel sheet, light grey Filter mat G3 acc.
to DIN EN 779, filtering degree 85% Filter material synthetic fibre with progressive construction, temperature resistant to 100°C, self-extinguishing class F1 moisture resistant to 100% RH, reusable – cleaning by washing or vacuuming Operating/ Storage temperature -45 to +70°C (-49 to +158°F) Protection type IP43 (with filter mat) / IP33 (without filter mat) Protection class I (earthed) Approvals UL Important note: For reasons of pressure compensation the roof filter fan must always be operated in combination with another filter fan (e.g.
Art.
No.
01803.0-00) or a passive intake filter (e.g.
Art.
No.
11803.0-00).
Roof Filter Fan - Dach-Filterlüfter RFP 018 Series Art.
No.
Operating Air volume, Air volume Power Average Depth in Enclosure Weight voltage w/ filter w/o filter noise level enclosure cut-out (approx.) Art.
Nr.
Betriebsspannung Kühlluftfördermenge/freiblasend Kühlluftfördermenge/free blowing Leistungs- Schalldruck Einbautiefe Montageausschnitt Gewicht aufnahme ISO4871 (ca.) 01860.0-00 AC 230 V, 50 Hz 300 m³/h (mit Filtermatte G3) 400 m³/h (ohne Filtermatte) 68 W 55 dB (A) 52 mm 250 x 250 mm +0,4 3,3 kg 01861.0-00 AC 230 V, 50 Hz 500 m³/h (mit Filtermatte G3) 650 m³/h (ohne Filtermatte) 64 W 67 dB (A) 107 mm 250 x 250 mm +0,4 2,6 kg 01860.0-02 AC 120 V, 60 Hz 345 m³/h (mit Filtermatte G3) 460 m³/h (ohne Filtermatte) 60 W 55 dB (A) 52 mm 250 x 250 mm +0,4 3,3 kg 01861.0-02 AC 120 V, 60 Hz 575 m³/h (mit Filtermatte G3) 748 m³/h (ohne Filtermatte) 85 W 67 dB (A) 107 mm 250 x 250 mm +0,4 2,6 kg Roof Exit Filter - Dach-Filterlüfter REP 118 Series Art.
No.
Depth in enclosure Enclosure cut-out Weight (approx.) Filter mat Protection type Art.
Nr.
Einbautiefe Montageausschnitt Gewicht (ca.) Filtermatte Schutzart 11860.0-00 11 mm 250 x 250 mm +0,4 1,0 kg G3 nach DIN EN 779, mittlerer Abscheidegrad 85 % IP43 (mit Filtermatte) (w/ filter mat) Filter Mats - Filtermatten FM 086 Filter mat - Filtermatte (3 St.) 282 x 282mm G3 (1 packing unit = 3 pcs.) Art.
No.
08613.0-00 Axiallüfter, Kugellager Lebensdauer min.
50.000 h bei 25 °C/77 °F (rF 65 %) Lüfterrahmen Aluminium, Rotor Kunststoff Anschluss 3-polige Klemme 2,5 mm², Anzugsmoment 0,8 Nm max.
Gehäuse Kunststoff nach UL94 V-0/ Stahlblech lackiert, lichtgrau Filtermatte G3 nach DIN EN 779, mittlerer Abscheidegrad 85 % Filtermaterial Kunststofffaser mit progressivem Aufbau, temperaturbeständig bis 100 °C, selbstverlöschend Klasse F1.
Feuchtigkeitsbeständig bis 100 % rF.
Einsatz-/ Lagertemperatur -45 bis +70 °C (-49 bis +158 °F) Schutzart IP43 (mit Filtermatte) / IP33 (ohne Filtermatte) Schutzklasse I (Schutzleiter) Approbationen UL Wichtiger Hinweis: Der Dach-Filterlüfter muss zum Druckausgleich im Schaltschrank immer in Kombination mit einem Eintrittsfilterlüfter (z.B.
Art.
Nr.
01803.0-00) oder einem Eintrittsfilter (z.B.
Art.
11803.0-00) betrieben werden.
Roof Filter Fan • Dach-Filterlüfter RFP 018 • 300m³/h , 500m³/h Roof Filter Fan (01860.0-xx) Dach-Filterlüfter (01860.0-xx) View from below Ansicht Unterseite Enclosure cut-out Montageausschnitt Hole centers Bohrlochabstand Roof Filter Fan (01861.0-xx) Dach-Filterlüfter (01861.0-xx)