18 18 TIGER ELECTRONICS THERMAL MANAGEMENT TIGER ELECTRONICS FANS + ACCESSORIES Technische Änderungen vorbehalten.
Alle Angaben ohne Gewähr.
Specifications are subject to change without notice.
Errors and omissions excepted.
1 m³/min = 35.3 CFM 1 Pa = 0.10197 mmH2O = 0.00401 inH2O Technische Änderungen vorbehalten.
Alle Angaben ohne Gewähr.
Specifications are subject to change without notice.
Errors and omissions excepted.
• Compact design • Double insulated • Integrated thermostat or hygrostat • Optional clip or screw fixing (CR130) The compact high performance fan heater prevents formation of condensation and provides an evenly distributed interior air temperature in enclosures with electric/electronic components.
The plastic enclosure provides double insulation and acts as protection against contact.
The fan heater is available with integrated thermostat or pre-set hygrostat for temperature or humidity control.
The CR 030 was designed as a stationary unit for the bottom of the enclosure.
For wall fixing the fan heater CR 130 is recommended.
• Kompakte Bauform • Schutzisoliert • Integrierter Thermostat oder Hygrostat • Wahlweise Clip- oder Schraubbefestigung (CR130) Hochleistungs-Heizgebläse zur gleichmäßigen Temperierung von Schränken und Gehäusen mit elektrischen/elektronischen Einbauten.
Durch den Einsatz des Heizgebläses werden Kondensat oder Frostbildung und damit Funkti- onsstörungen vermieden.
Das Kunststoffgehäuse schützt vor Berührung elektrischer sowie heißer Einbauteile.
Das Heizgebläse ist mit integriertem Temperaturregler, einstellbar 0 bis 60 °C, oder fest eingestelltem Hygrostat lieferbar.
Das Gerät ist für die Befestigung am Gehäuseboden vorgesehen.
Für die Wandbefestigung eignet sich das Heizgebläse CR 130.
Heating element high performance cartridge Temperature safety cut-out to protect against overheating in case of fan failure Heater body extruded aluminium profile Axial fan, ball bearing airflow 160m³/h, free flow service life 50,000h at 25°C (77°F) Casing plastic according to UL94 V-0, black Connection 2-pole max.
2.5mm², clamping screw with strain relief, torque 0.8Nm max.
Mounting screw fixing (M5) Fitting position horizontal Operating*/ Storage temperature 0 to +60°C (+32 to +140°F) / -45 to +70°C (-49 to +158°F) Dimensions 168 x 145 x 100mm Weight approx.
1.40kg Protection type/ Protection class IP20 / II (earthed) Note: other heating capacities from 200W up available on request Art.
No.
Model Operating voltage Heating capacity Setting range Approvals Art.-Nr.
Ausführung Betriebsspannung Heizleistung Einstellbereich Approbationen 03051.0-00 Fan Heater with thermostat 230VAC, 50/60Hz 950W 0 to +60°C VDE + UL File No.
E234324* Heizgebläse mit Thermostat 03051.0-02 Fan Heater with hygrostat 230VAC, 50/60Hz 950W 65% RH, factory-set VDE + UL File No.
E234324* Heizgebläse mit Hygrostat 65% rF fest eingestellt 03051.9-00 Fan Heater with thermostat 120VAC, 50/60Hz 950W 0 to +60°C UL File No.
E234324* Heizgebläse mit Thermostat 13051.0-00 Fan Heater with thermostat 230VAC, 50/60Hz 950W 0 to +60°C VDE + UL File No.
E234324* Heizgebläse mit Thermostat 13051.0-02 Fan Heater with hygrostat 230VAC, 50/60Hz 950W 65% RH, factory-set VDE + UL File No.
E234324* Heizgebläse mit Hygrostat 65% rF fest eingestellt 13051.9-00 Fan Heater with thermostat 120VAC, 50/60Hz 950W 0 to +60°C UL File No.
E234324* Heizgebläse mit Thermostat *according to UL499 in combination with UL508A Compact high-performance Fan Heater • Kompaktes Hochleistungs-Heizgebläse CR 030 / CR 130 • 950W, 700W Heizelement Hochleistungsheizpatrone Temperaturwächter Überhitzungsschutz bei Lüfterausfall mit automatischer Rückschaltung Heizkörper Aluminiumprofil Axiallüfter, Kugellager Luftleistung 160 m³/h, freiblasend Lebensdauer 50.000 h bei 25 °C (77°F) Gehäuse Kunststoff nach UL94 V-0, schwarz Anschluss 2-polig max.
2,5 mm² mit Zugentlastung, Klemmschraube Anzugsmoment 0,8 Nm max.
Befestigung Schraubbefestigung (M5) Einbaulage horizontal Einsatz-*/ Lagertemperatur 0 bis +60 °C (+32 bis +140 °F) / -45 bis +70 °C (-49 bis +158 °F) Abmessungen 168 x 145 x 100 mm Gewicht ca.
1,40 kg Schutzart/ Schutzklasse IP20 / II (schutzisoliert) Hinweis andere Heizleistungen ab 200 W auf Anfrage CR030 Connection diagramm Anschlussbild CR130 CR030 CR130 CR030: CR130: *Operating temperature of heater with integrated hygrostat: 0 to +60°C (+32 to +140°F) *Einsatztemperatur der Heizung mit integriertem Hygrostat: 0 bis +60 °C (+32 bis +140 °F) L L N N M 30 182 142 99 160 67