Mechanical Hygrostat • Mechanischer Hygrostat MFR 012 • Adjustable relative • Change-over contact • High switching capacity • Easily accessible terminals • Clip fixing The electromechanical thermostat MRF 012 is designed to control enclosure heaters so that the dew point is raised when a critical relative humidity of 65% is exceeded.
In this way condensation and corrosion is effectively prevented.
• Einstellbare relative Feuchte • Wechselkontakt • Hohes Schaltvermögen • Klemmen leicht zugänglich • Clip-Befestigung Der mechanische Hygrostat wird zur Regelung von Heizungen/Heizlüftern eingesetzt, um durch die Temperaturerhöhung den Taupunkt ab einer kritischen Luftfeuchtigkeit von 65 % relativer Luftfeuchtigkeit in Schränken/Gehäusen mit elektrischen/elektronischen Einbauten anzuheben.
Dadurch wird verhindert, dass sich an Bauteilen und Einbauten Kondensat niederschlägt.
Art.
No.
Setting range Art.
Nr.
Einstellbereich 01220.0-00 35 to 95% RH / 35% bis 95% rF Load 1 = Enclosure heater Load 2 = Air humidifier Last 1 = Schaltschrankheizung Last 2 = Luftbefeuchter Switch difference* 4% RH (± 3% tolerance) permissible air velocity 15m/sec Contact type change-over contact Contact resistance 10m? Service life 50,000 cycles Min.
Switching capacity 20V AC/DC, 100mA Max.
Switching capacity 250VAC, 5 (0.2) A DC 20W EMC acc.
to EN 55014-1-2, EN 61000-3-2, EN 61000-3-3 Connection 3-pole terminal for 2.5mm², clamping torque 0.5Nm max.: rigid wire 2.5mm² stranded wire (with wire end ferrule) 1.5mm² Mounting clip for 35mm DIN rail, EN50022 Casing plastic according to UL94 V-0, light grey Dimensions 67 x 50 x 38mm Weight approx.
60g Fitting position variable Operating / Storage temperature 0 to +60°C (+32 to +140°F) / -20 to +80°C (-4 to +176°F) Protection type IP20 Approvals VDE and UL *at 50% RH Schaltdifferenz (Feuchtigkeit)* 4 % rF (± 3 % Toleranz) zulässige Luftgeschwindigkeit 15 m/Sek.
Kontaktart Wechsler mit Sprungkontakt Kontaktübergangswiderstand 10 m? Lebensdauer 50.000 Zyklen Min.
Schaltleistung AC/DC 20 V, 100 mA Max.
Schaltleistung AC 250 V, 5 (0,2) A DC 20 W EMV nach EN 55014-1-2, EN 61000-3-2, EN 61000-3-3 Anschluss 3-polige Klemme, Anzugsmoment 0,5 Nm max.: Starrdrahtleitung 2,5 mm² Litzenleitung mit Aderendhülse 1,5 mm² Befestigung Clip für 35 mm DIN-Schiene, EN 50022 Gehäuse Kunststoff nach UL94 V-0, lichtgrau Abmessungen 67 x 50 x 38 mm Gewicht ca.
60 g Einbaulage beliebig Einsatz-/Lagertemperatur 0 bis +60 °C (+32 bis +140 °F) / -20 bis +80°C (-4 bis +176°F) Schutzart IP20 Approbationen VDE und UL *bezogen auf 50 % rF