50 50 TIGER ELECTRONICS THERMAL MANAGEMENT TIGER ELECTRONICS FANS + ACCESSORIES Technische Änderungen vorbehalten.
Alle Angaben ohne Gewähr.
Specifications are subject to change without notice.
Errors and omissions excepted.
1 m³/min = 35.3 CFM 1 Pa = 0.10197 mmH2O = 0.00401 inH2O Technische Änderungen vorbehalten.
Alle Angaben ohne Gewähr.
Specifications are subject to change without notice.
Errors and omissions excepted.
Electronic Hygrotherm • Elektronischer Hygrotherm ETF 012 • Temperature and humidity adjustable • Optical operating display (LED) • High switching capacity • Clip fixing The electronic hygrotherm senses the ambient temperature and relative humidity in an enclosure with electric/electronic components, and turns on a heater (or alternatively, a fan) at either set point, helping prevent the formation of condensation in the enclosure.
The LED integrated in the adjustment knob on the active controller is lit when the connected device is in operation.
• Temperatur und Luftfeuchtigkeit einstellbar • Optische Betriebsanzeige (LED) • Hohe Schaltleistung • Clip-Befestigung Der elektronische Hygrotherm überwacht gleichzeitig Temperatur und relative Feuchte in Schränken und Gehäusen mit elektrischen/elektronischen Einbauten und schaltet bei Erreichen der eingestellten Werte (Temperatur oder relative Luftfeuchtigkeit) eine Hei- zung oder einen Lüfter ein.
Dadurch wird Kondensat an Bauteilen und elektronischen Komponenten verhindert.
Die in den Einstellknöpfen integrierten LEDs leuchten, wenn die angeschlossene Heizung oder Lüfter in Betrieb ist.
Connection diagramm Anschlussdiagramm Anschlussbeispiel Example of connection Heater Heizung Hygrotherm ETF012 Heater Heizung Switch difference (temperature) 2K (± 1K tolerance) Switch difference (humidity) 4% RH (± 1% tolerance) Reaction time (humidity) approx.
5 sec.
Contact type change-over contact (relay) Contact resistance 10m? Service life NC: 50,000 cycles NO: 100,000 cycles Max.
Switching capacity (Relay NC: 240VAC, 6 (1) A output) NO: 240VAC, 8 (1.6) A NC: 120VAC, 6 (1) A NO: 120VAC, 8 (1.6) A 24VDC, 4A EMC acc.
to EN 55014-1-2, EN 61000-3-2, EN 61000-3-3 Optical indicator LED Connection 5-pole terminal, clamping torque 0.5Nm max.: rigid wire 2.5mm² stranded wire (with wire end ferrule) 1.5mm² Mounting clip for 35mm DIN rail, EN50022 Casing plastic according to UL94 V-0, light grey Dimensions 77 x 60 x 43mm Weight approx.
0.20kg Fitting position vertical Operating / Storage temperature 0 to +60°C (+32 to +140°F) / -20 to +80°C (-4 to +176°F) Protection type IP20 Schaltdifferenz (Temperatur) 2 K (± 1 K Toleranz) Schaltdifferenz (Feuchtigkeit) 4 % rF (± 1 % Toleranz) Ansprechzeit (Feuchtigkeit) ca.
5 Sek.
Kontaktart Wechsler (Relais) Kontaktübergangswiderstand 10 m? Lebensdauer Öffner (NC): 50.000 Zyklen Schließer (NO): 100.000 Zyklen Max.
Schaltleistung (Relaisausgang) NC: AC 240 V, 6 (1) A NO: AC 240 V, 8 (1,6) A NC: AC 120 V, 6 (1) A NO: AC 120 V, 8 (1,6) A DC 24 V, 4 A EMV EN 55014-1-2, EN 61000-3-2, EN 61000-3-3 Betriebsanzeige LED Anschluss 5-polige Klemme, Anzugsmoment 0,5 Nm max.: Starrdrahtleitung 2,5 mm² Litzenleitung mit Aderendhülse 1,5 mm² Befestigung Clip für 35 mm DIN-Schiene, EN 50022 Gehäuse Kunststoff nach UL94 V-0, lichtgrau Abmessungen 77 x 60 x 43 mm Gewicht ca.
0,20 kg Einbaulage vertikal Einsatz-/Lagertemperatur 0 bis +60 °C (+32 bis +140 °F) / -20 bis +80°C (-4 bis +176°F) Schutzart IP20 Art.
No.
Operating voltage Setting range temperature Setting range humidity Approvals Art.
Nr.
Betriebsspannung Einstellbereich Temperatur Einstellbereich Feuchtigkeit Approbationen 01230.0-00 230VAC, 50/60Hz 0 to +60°C 50 to 90% RH VDE + UL 01230.9-00 120VAC, 50/60Hz +32 to +140°F 50 to 90% RH UL 01230.9-01 120VAC, 50/60Hz 0 to +60°C 50 to 90% RH UL